What size breaker does that appliance need?

Pick your country and the appliance. You get the current it draws, the circuit breaker it needs, and whether it can plug in or must be hard-wired.

1

Where are you?

2

What's the appliance?

Typical ratings shown
3

Power rating

Electrician options
Supply

1.00 for heating elements. Motors and compressors run lower.

Load type

Common appliances at a glance

Typical ratings for large appliances in your country. Tap a row to load it into the calculator. Always check the rating plate on the actual model.

ApplianceTypical powerVoltageCurrentBreaker

How the current is worked out

Single-phase current is power divided by voltage: I = P ÷ (V × PF). On three-phase it's I = P ÷ (√3 × V × PF), using the line-to-line voltage.

How the breaker is picked

The breaker is the smallest standard size at or above the design current. Loads that run for 3 hours or more get a 125% allowance, which the NEC requires in North America and is good practice everywhere.

Before you buy

Check the rating plate or spec sheet for the input power, then check your switchboard has a spare way and enough supply capacity. Large appliances often need a new circuit.

Common questions

How do I work out how many amps an appliance uses?

Divide the power in watts by the supply voltage. A 2400 W heater on 230 V draws 2400 ÷ 230 = 10.4 A. On 120 V the same heater would draw 20 A.

What size breaker do I need for a 3.6 kW hot water system?

At 230 V a 3.6 kW element draws about 15.7 A. Because a storage tank heats for hours, a 20 A breaker on 2.5 mm² cable is the usual choice in Australia and New Zealand.

Can I plug a 2400 W heater into a normal power point?

In Australia and New Zealand, yes. Appliances are rated at 240 V, so 2400 W is 10 A, which suits a standard 10 A power point. Avoid running it from a power board or extension lead.

Should I use the cooling capacity or input power for an air conditioner?

Use the electrical input power. A 7 kW split system typically draws around 2 to 2.5 kW of electricity. If the installation manual gives a breaker size, use that.

Why is the recommended breaker bigger than the current draw?

Loads that run for three hours or more, such as hot water, heaters and EV chargers, are sized at 125% of their current. Breakers in an enclosed switchboard run warm, and this allowance stops nuisance tripping.